Tóm tắt tài liệu kỹ thuật
Testomat 2000 Polymer
Engineering summary from PDF text extraction for Testomat 2000 Polymer. Verify every value with the OEM datasheet.
Summary
Product identification
The Testomat 2000® Polymer is a wet-chemical online monitor for polyacrylate content.
Application
- Monitoring of conditioning agents in cooling and heating circuits.
Operating limits
- Ambient temperature: 10–45 °C (50 - 104°F)
- Water temperature: 10 to 40 °C (50 to 104°F)
- Operating pressure:
- 1 to 8 bar (15 to 116 psi) or
- 0.3 to 1 bar (5 to 15 psi) (after removing the valve body from the regulator/filter housing).
Feed water
- Water inlet hose: 6 mm external diameter / 4 mm internal diameter.
Product water
- Water outlet hose: 6 mm external diameter / 4 mm internal diameter.
Measuring range
- 0 to 50 mg/l (ppm) (with the factor set to 1.00).
- Customer specific ranges are possible, e.g., 0.0-50.0 mg/l.
Technical Data
Electrical
- Power supply: 230–240 VAC, 115 VAC, 24 VAC (all 50–60Hz)
- Power consumption: max. 30 VA
- Protection class: I
Mechanical / hydraulic
- Dimensions (W x H x D): 380 x 480 x 280 mm
- Weight: approx. 9.5 kg
- Degree of protection: IP 65
- Menu languages: German, English (others upon request)
Disclaimer: Extraction may miss figures, footnotes, or revisions; contractual data must match the OEM PDF revision used on the project.