Quay lại Testomat
Testomat logo

Tóm tắt tài liệu kỹ thuật

Titromat KH

Engineering summary from PDF text extraction for Titromat KH. Verify every value with the OEM datasheet.

Summary

Product identification

Titromat® KH is used for automatically determining and monitoring the carbonate hardness for high hardness measuring ranges.

Application

  • Alkalinity of open coolant circuits

Measuring range

  • 5 - 150 °KH (resolution 5)
  • 2 - 60 °KH (resolution 2)

Technical Data

  • Power supply: 230–240 VAC, 115 VAC, 24 VAC all 50–60Hz
  • Power consumption: max. 30 VA
  • Protection class: I
  • Degree of protection: IP 65
  • Ambient temperature: 10–45 °C, 50 - 104°F
  • Dimensions (W x H x D): 380 x 480 x 280 mm
  • Weight: approx. 9.5 kg
  • Menu languages: German, English, French (others upon request)

Mains water supply

  • Operating pressure: Depending on product configuration:
    • 0.3 – 1 bar / 0.3 x 10⁵ to 1 x 10⁵ Pa
    • 1 - 4 bar / 1 x 10⁵ to 4 x 10⁵ Pa
    • (a pressure reducer (special accessory) should be used from 4 to 8 bar range)
  • Water inlet: Opaque hose with 6 mm external diameter / 4 mm internal diameter
  • Water outlet: Hose with 6 mm external diameter / 4 mm internal diameter
  • Water temperature: 10 to 40 °C; 50 to 104°F

Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.