Tóm tắt tài liệu kỹ thuật
Picomag-DMA
PDF datasheet mirror for Picomag-DMA (Endress + Hauser Flow measurement). Verify with OEM before design.
Summary
Product identification
Product: Picomag electromagnetic flowmeter Product headline: Smart magmeter for utilities – intuitive · convenient · multivariable. Field of application: Economical magmeter for conductive liquids in secondary circuits across various industries.
Operating limits
- Max. process pressure: 16 bar
- Medium temperature range: -10 to 70°C (+14 to +158 °F)
- Permissible short-term temperature (max. one hour): 85 °C (185 °F) (Repetition after 4 hours at the earliest)
- Ambient temperature range: -10 to 60 °C
Feed water
- Liquids: Conductive liquids
Product water
- Measured variables: Volume flow, Temperature, Conductivity
- Max. measurement error (Volume flow): +/-0.8% o.r. +/- 0.1% o.f.s
- Measuring range (Volume flow): up to 750 l/min
Electrical
- Power supply: 18 to 30V DC
- Outputs: Current (4 to 20mA), Pulse, Switch, Voltage (2 to 10V)
- Inputs: Status
- Digital communication: IO-Link
Mechanical / hydraulic
- Nominal diameter range: DN15 to 50 (1/2 to 2")
- Wetted materials: PEEK, Stainless Steel, FKM, EPDM
- Electrodes: 1.4404/316L
- Sensor housing material: 1.4404/316L, Polycarbonate
- Transmitter housing material: 1.4404/316L, Polycarbonate
- Degree of protection: IP 65/67
Features
- Simultaneous flow, conductivity, and temperature measurement.
- Space-saving design with sensor and transmitter in one housing.
- Intuitive operation and configuration via SmartBlue App using Bluetooth.
- Quick offline configuration check with "knock" functionality.
- High shock and vibration resistance.
- Empty pipe detection.
- Flexible integration with IO-Link and various I/Os.
- 1.4" TFT color display with backlight.
- cULus listing.
- NSF drinking water approvals.
Disclaimer: Extraction may miss figures, footnotes, or revisions; contractual data must match the OEM PDF revision used on the project.
Official datasheet (PDF)
Nội dung tổng hợp từ tài liệu kỹ thuật công khai nhằm tra cứu và so sánh sơ bộ. Bản tóm tắt không thay thế bảng dữ liệu hiện hành được nhà sản xuất chứng nhận. Kiểm tra phiên bản và giới hạn thiết kế trước khi sử dụng.